Something You Should Know about Cooling FAN

modir 1403/03/30
CollingFan 4

Date:2020/09/30

By: Peter Cheng /RMA
peter@meanwell.com


 

Dedicated to power supply after-sales service for more than a decade, I feel honored to witness the power supply industry’s evolution in both the circuit design technology and the compact parts size. Under this trend, the power density of the power supply has been continuously improved, and so is the product volume.
 

To achieve the high power density for high-wattage power supplies, the heat dissipation issue is non-negligible. The easiest solution is to implement a fan to enhance heat dissipation. To enhance the efficiency of the fan, the wind direction of the fan is changed from suck-out to blow-in, a change that both the temperature of the components and the internal space volume of the product can be greatly reduced. However, because of the unsynchronized customer’s habits, such design change relatively brings other issues.
  

Common problems for FAN with blow-in direction

CollingFan 1

Figure 1. Dust accumulated on iron net

Dust floating in the air is sucked by the fan and attached to the iron net. Accumulating over time, the amount of dust jams the iron net, a fact that causes insufficient air intake and lead to a serious downgrade effect on heat dissipation. Moreover, the jam situation can trigger the “FAN LOCK” function, shutting down the machine.


 

CollingFan 2

Figure 2. Dust accumulated at windward side

Dust accumulated between components at the windward side caused insufficient heat dissipation. If moisture is absorbed at the same time, it is possible to cause a decrease of withstand voltage, arcing or short-circuit between components can be expected.


 

CollingFan 3

Figure 3. Arcing caused by dust and moisture

The original design of the distance between the two high-voltage copper foils fulfills safety requirement, but it no long the same if dust accumulated over the time. When those dusts absorb moisture, which will cause the resistance dropped, and finally causing arcing.


 

Comparison between two different wind direction 
 

Wind directionAdvantageDisadvantageApplication
Blow-inHigh performance in heat dissipation
Not require extra heat dissipation designs
Compact volume
Affected by environmental issues, moisture
High possibility of arcing at the windward
Accumulated Dust on FAN
Corrosion of metal parts
Engine room
Suck-outMid-level performance in heat dissipation
Affected by environment less
Less dust accumulation issue
Longer product lifecycle affected by environmental issues, moisture
Higher internal temperature
Larger volume
Open field Cabinet
Factory
 

Changing customer’s habits regarding the existing design of the blow-in structure of the product is not easy. How to strike a balance between the two? It has become a major task for designers.
 

MEAN WELL developed a new generation of fanless, conduction cooling power supply, UHP series, the best choice for customers. The unique fanless design perfectly solves the customer’s headaches regarding fan failures caused by absorbing dusts, and it can reduce the frequency and cost of device maintenance. Fanless design can also solve fan noise level issues, thus making the UHP-2500 extremely suitable for the environment that requires absolute quietness.

UHP-2500-24

Fanless UHP series covers 200~2500W


 

Product features

StructureAdvantageApplication
Fanless
Convention cooling
Wide application usage
Low cost
No extra power consumption
Noise and vibration-free
Low maintenance fee
Easy installation
Low power density application
Application requires noise and vibration-free such as medical device, indoor lighting, security system, and precision instrument
 

For further fanless design information, please refer to :
منابع تغذیه بدون فن و کاربردهای آن

بدون دیدگاه
اشتراک گذاری
اشتراک‌گذاری
با استفاده از روش‌های زیر می‌توانید این صفحه را با دوستان خود به اشتراک بگذارید.